Amps to kW
Put this tool on your site. Paste the code into any page or blog post. No sign-up, no ads inside, and it sizes itself.
Pick the current type, enter amps and volts, and read the kilowatts. The input people forget is power factor, and the direction it works in is the thing that trips almost everyone up: amps times volts gives you apparent power, not real power. Real power is the part actually turned into heat, torque or light, and you get to it by multiplying the apparent power BY the power factor — not dividing by it. That is the opposite of what you do converting kW back to amps, which is why so many people get the same circuit wrong in one direction and right in the other. A 50 A single-phase load at 240 V is 12 kVA of apparent power but only 9.6 kW of real power at a 0.8 power factor. This tool shows both numbers side by side, prints the formula with your values substituted, and hides the power-factor field entirely in DC mode, because DC doesn't have one.
How to use
- 1
Pick the current type. DC is for battery banks, solar arrays, and DC drives — there's no power factor, so the field disappears. AC single-phase covers homes, small shops, and most loads under about 7 kW. AC three-phase covers commercial HVAC, industrial machines, and anything on a three-phase service; choose line-to-line (L-L) if your voltage is the phase-to-phase figure (208, 400, 480 V — the usual case), or line-to-neutral (L-N) if the spec quotes the voltage from one line to neutral (120, 230, 277 V).
- 2
Enter the current in amperes. This is what the load actually draws — a clamp-meter reading, a nameplate FLA figure, or the breaker size you're checking a load against. If you're working from a breaker rating, remember a breaker is sized above the continuous load, not at it, so the kW you get back is a ceiling rather than the real consumption. Decimals are fine (1.5 A, 0.25 A).
- 3
Set the power factor. Unity (1.0) is right for resistive loads — heaters, incandescent lamps, kettles. Use about 0.95 for LED drivers and modern switch-mode supplies, 0.85 for induction motors at full load, and 0.8 as the conventional planning default when you genuinely don't know. Power factor is a ratio between 0 and 1, not a percentage — enter 0.8, not 80. Tap a chip to fill the field.
- 4
Read the real power, the watts, and the apparent power. The big number is kilowatts at four significant figures, with the same figure in watts underneath for smaller loads. When the power factor isn't 1, the apparent power in kVA appears as well — that's the larger number, and it's the one a generator, UPS or transformer has to be sized against. The formula line shows the calculation with your values plugged in; copy the number alone or the whole formula with the buttons beside it.